Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

09/23/19

Message Overview:

Fault Message:

OPEN CKT-INLET DOOR XDCR/SEC VA WRG

Fault Code:

4960315APU

Associated CAS:

APU DOOR FAIL
(Caution)

APU SHUTDOWN
(Advisory)

Reporting LRU: Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC)
System Description: 49-60-00
Schematic Diagram: 49-61-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 49-12-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]
49-61-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

The Full-Authority Digital Engine-Controller (FADEC) commanded an Auxiliary Power Unit (APU) shut down, or failure to start, because the FADEC received a signal from the inlet door Rotary Variable Differential Transducer (RVDT) that was out of the expected range.

Possible Causes:

  • Inlet-Door Rotary Transducer (RVDT) (MT5)
  • Auxiliary Power Unit (APU) Full-Authority Digital Engine-Controller (FADEC) (A108)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

If CAS message is not active, verify stored faults on CAIMS.

Quick Links:

Access to Active Faults AMM 45-45-00-970-802 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Access to Stored Faults AMM 45-45-00-970-803 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Access to System Diagnostics AMM 45-45-00-970-804 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Engine Branched Wiring-Harness AMM 49-12-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Engine Branched Wiring-Harness AMM 49-12-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Inlet-Door Rotary Transducer AMM 49-14-09-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Inlet-Door Rotary Transducer AMM 49-14-09-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Full-Authority Digital Engine-Controller (FADEC) AMM 49-61-01-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Full-Authority Digital Engine-Controller (FADEC) AMM 49-61-01-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. Access CAIMS and using active faults, or stored faults, find the fault and verify the CAS message. You can use System Diagnostics to view each channel of the APU FADEC (each sensor) in real time, and also access ground faults. Page 2 of the APU DATA STATUS shows the APU inlet door position.
  2. Verify Visually that the APU inlet door is accurate to the CAIMS readings.
  3. Inspect the wiring and connectors to the inlet-door rotary transducer for any damage.

    1. If damages are found, repair as required and do close out.
    2. If damages are not found, continue with next step.

  4. Inspect the transducer (RVDT) for condition and perform continuity check on transducer connector (P804) as follows:

    From To Expected Result Result
    P804-4 P804-6 <1000 ohms

    1. If the resistance check is not as mentioned above, repair defective wiring as required and do close out.
    2. If the resistance check is as mentioned above, continue with next step.

  5. Perform continuity check between the transducer connector (P804) and grounded shell as follows:

    From To Expected Result Result
    P804-4 Ground >1 megaohm
    P804-6 Ground >1 megaohm

    1. If the resistance check is not as mentioned above, replace defective inlet door rotary transducer and do close out.
    2. If the resistance check is as mentioned above, continue with next step.

  6. Re-rack FADEC and verify connector A108AP1-A8 and A108AP1-B8 for damage or FOD.

    1. If damages are found, repair as required and do close out.
    2. If damages are not found, continue with next step.

  7. Perform wiring checks between APU FADEC connector A108AP1 and the transducer connector J804.

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  8. Replace the APU FADEC.
  9. Do close out.