Message Overview:
Message Name:
GEN3 [DIFF PROTECTION FEEDER]
Message Code:
2423124LPS
Associated CAS:
| Reporting LRU: | Variable Frequency Generator (VFG) 3 |
| System Description: | 24-21-00 - Primary AC Power Supply |
| Schematic Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] SSM 24-21-00-101 - Primary AC Power Supply System - Electrical Schematic |
| Wiring Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] WM 24-21-00 - Generator Control No. 3 - ALL |
Message Description:
Variable Frequency Generator (VFG) 3 has tripped off-line or will not come on-line.
Possible Causes:
- AC Power Center (ACPC) (A54)
- Generator Control Unit (GCU) 3 (A58)
- Variable Frequency Generator (VFG) 3 (G3)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-24-0598 - Variable Frequency Generator (VFG) GL511-1103-9 - Failure
- AW700-24-0572 - "GEN FAIL" associated with fault message "Open Circuit TR2/TR3"
- AW700-24-0655 - Variable Frequency Generator Harness Low Clearance to Hydraulic/Fuel Lines
Full Throttle Blog/Forum Articles/Infoservice/Newsletter:
- REFERENCE INSTRUCTION LETTER (RIL) GX-0198 - Return to service following VFG bearing failure and/or VFG housing rupture
Flight Operation Notifications Manual (FONM): None
NOTES:
- Prior to T/S procedures, perform a visual of generator 3 for heat distress. Confirm if the heat exchanger is blocked with FOD.
- A GCU patch cable (GSE REF # 24X-24-02) can be used to interchange GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only).
- The GCU NVMs can only be downloaded at position #2 or #3.
Quick Links:
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Access CAIMS and check if the following faults are active:
- 2423126LPS - GEN3 OIL OVERTEMP FAULT
- 2423200LPS - GEN3 DRIVE SHAFT FAIL/INVALID %N2
Inspect the VFG for the following:
- VFG oil filter bypass indicator tripped, and/or
- Metal particles in the oil lines, and/or
- VFG end frame cracked or breached, and/or
- Oil sight glass cracked
- If there is a combination of the listed CAIMS active fault and VFG condition(s) perform RIL GX-0198
- If there is NO combination, continue with next step.
- Access CAIMS active fault. Are there any ACPC related faults?
- If YES, troubleshoot these messages first.
- If NO, continue with next step.
- Interchange the GCU 3 with GCU 2 (physically or using the GCU patch cable).
NOTE: Use PMAT to monitor the fault on GCU.- If system checks are good, replace GCU 3 and do close out.
- If fault remains, continue with next step.
- Disconnect GCU 3 connector A58P2 and VFG 3 connector G3P1. Do a continuity check as follows:
From To Result A58P2-41 Ground A58P2-42 Ground A58P2-50 Ground A58P2-40 Ground - If there is continuity, repair defective wiring as required.
- If there is NO continuity, continue with next step.
- Do a continuity check between GCU 3 and VFG 3 as follows:
From To Result A58P2-41 G3P1-F A58P2-42 G3P1-E A58P2-50 G3P1-J A58P2-40 G3P1-D - If there is continuity, continue with next step.
- If there is NO continuity, repair defective wiring as required.
- Disconnect ACPC connector A54P3. Do a continuity check as follows:
From To Result A58P2-49 Ground A58P2-57 Ground A58P2-63 Ground A58P2-62 Ground - If there is continuity, repair defective wiring as required.
- If there is NO continuity, continue with next step.
- Do a continuity check between GCU 3 and ACPC as follows:
From To Result A58P2-49 A54P3-E A58P2-57 A54P3-F A58P2-63 A54P3-G A58P2-62 A54P3-H - If there is continuity, continue with next step.
- If there is NO continuity, repair defective wiring as required.
- Disconnect VFG #3 (T1, T2 and T3) and ACPC VFG3-A, B and C.
- Do an Insulation check using a megger as follows:
Caution: Before using the megger, make sure both sides of cable are disconnected. Failure to do that may damage the equipmentFrom To Expected Result Result VFG3-T1 Ground No Continuity VFG3-T2 Ground No Continuity VFG3-T3 Ground No Continuity - If there is continuity repair defective wiring and do close out.
- If there is no continuity, continue with next step.
- Do an Insulation check using a megger as follows:
Caution: Before using the megger, make sure both sides of cable are disconnected. Failure to do that may damage the equipmentFrom To Expected Result Result VFG3-T1 VFG3-T2 No Continuity VFG3-T1 VFG3-T3 No Continuity VFG3-T1 VFG3-G No Continuity VFG3-T2 VFG3-T3 No Continuity VFG3-T2 VFG3-G No Continuity VFG3-T3 VFG3-G No Continuity - If there is continuity repair defective wiring and do close out.
- If there is no continuity, continue with next step.
- Do a continuity check as follow:
From To Expected Result Result VFG3-T1 ACPC VFG3-A Continuity VFG3-T2 ACPC VFG3-B Continuity VFG3-T3 ACPC VFG3-C Continuity VFG3-G Ground Continuity - If there is continuity, continue with next step.
- If there is no continuity, repair defective wiring as required.
- Interchange VFG 3 and VFG 4. Is the fault still present?
- If YES, continue with next step.
- If NO, replace defective VFG.
- Replace ACPC.
- Do close out.