Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

07/01/24

Message Overview:

Message Name:

SLAT RIGHT RESOLVER/ SFCU/ WRG

Message Code:

2750014STD

Associated CAS:

SLAT FAIL
(Caution)

SLAT FAULT
(Caution)

SLAT FLAP FAIL
(Caution)

SLAT FLAP FAULT
(Caution)

SLAT FLAP HALFSPD
(Advisory)

SLAT HALFSPD
(Advisory)

Reporting LRU: Slat/Flap Control Unit (SFCU)
System Description: 27-52-00 - Leading Edge Slat System
Schematic Diagram: 27-50-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 27-50-01 [ Global Express ]  [ G5000 ]  [ Global XRS ]
27-50-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]
27-50-06 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Message Description:

The Slat/Flap Control Unit (SFCU) does not receive input from the Right Wing Slat Resolver or the input is not in the permitted range.

Possible Causes:

  • Right Slat Resolver (MT78)
  • Slat/Flap Control Unit (SFCU) 1 (A124)
  • Slat/Flap Control Unit (SFCU) 2 (A95)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin:

  • AW 700-27-0373 - SFCU -17: “SLAT-FLAP HALFSPD” EICAS Nuisance Message

Forum Articles/Infoservice/Newsletter: None

Flight Operation Notifications Manual (FONM): None

NOTES:

  • The resolvers are used by the SFCU for surface position acquisition.

Quick Links:

Removal of the Slat/Flap Control Unit (SFCU) AMM 27-51-05-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Slat/Flap Control Unit (SFCU) AMM 27-51-05-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Slat Resolvers AMM 27-53-41-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Slat Resolvers AMM 27-53-41-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. On the EMS CDU, select CTRL function and SLAT/FLAP RESET.
  2. NOTE: Wait at least one minute after SFCU reset to allow self-test to run.
  3. Cycle the SLATs from IN/0 degrees to OUT/30 degrees.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  4. Swap SFCU 2 with SFCU 1.

    1. If system checks are good, replace SFCU 2 and do close out.
    2. If fault remains, continue with next step.

  5. Move the SFCL to a different detent.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.
      NOTE: SFCU 1 is the right side (channel 1) controller. SFCU 2 is the right side (channel 2) controller.

  6. Perform a resistance check from the applicable resolver channel SFCU rack connector through the Right Slat resolver as follows:

    From the SFCU 1, (resolver channel 1):

    From To Expected Result Result
    A124AP1-13 A124AP1-14 140 to 220 ohms (Resolver Primary Coil R2-R1)
    A124AP1-36 A124AP1-37 13 to 24 ohms (Output Sine Coil ch. 1)
    A124AP1-49 A124AP1-50 13 to 24 ohms (Output Cosine Coil ch.1)

    From the SFCU 2, (resolver channel 2):

    From To Expected Result Result
    A95AP1-13 A95AP1-14 140 to 220 ohms (Resolver Primary Coil R2-R1)
    A95AP1-36 A95AP1-37 13 to 24 ohms (Output Sine Coil ch. 1)
    A95AP1-49 A95AP1-50 13 to 24 ohms (Output Cosine Coil ch. 1)

    1. If resistance is within range, go to step 7.
    2. If fault remains, continue with next step.

  7. Perform wiring checks between the applicable SFCU rack connector and the Right SLAT resolver connector.
    From the SFCU 1, (resolver channel 1):

    From To Expected Result Result
    MT77-1 A124AP1-2 Continuity
    MT77-2 A124AP1-1 Continuity
    MT77-6 A124AP1-34 Continuity
    MT77-5 A124AP1-33 Continuity
    MT77-3 A124AP1-47 Continuity
    MT77-4 A124AP1-46 Continuity

    From the SFCU 2, (resolver channel 2):

    From To Expected Result Result
    MT77-7 A95AP1-2 Continuity
    MT77-8 A95AP1-1 Continuity
    MT77-12 A95AP1-34 Continuity
    MT77-11 A95AP1-33 Continuity
    MT77-9 A95AP1-47 Continuity
    MT77-10 A95AP1-46 Continuity

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  8. Replace Right wing SLAT resolver.
  9. Do close out.